Product specifications

The Beckhoff EL3413-0001 measures three-phase electrical quantities with galvanically isolated current inputs. This 600 V variant supports network analysis; neutral-conductor current measurement is standard on units from the third quarter of 2015.

Manufacturer
Beckhoff
Manufacturer part number
EL3413-0001
Product type
EtherCAT power measurement terminal
Measuring voltage
600 V AC three-phase maximum; phase-to-neutral maximum 346 V AC; overvoltage category II
Measuring current
5 A AC maximum, configurable; via x A/5 A measuring transformers
Electrical isolation
4500 V between connection terminal and E-bus